DSE controllers show this as a text alarm on the display, not as a numbered code.
The generator is absorbing power from the grid instead of supplying it. This dangerous condition occurs when engine power drops below the power required to overcome system losses, causing the generator to act as a motor.
Need parts? Call us with your engine or controller model and we will confirm what we can supply and when.Call +254 768 860 665
Reverse power (motoring) occurs when the generator absorbs power from the grid instead of producing it. This can damage the prime mover and must trigger immediate disconnection.
Typical reverse power trip is set at 5-15% of rated power with a time delay of 2-5 seconds. Settings depend on application and generator characteristics.
Send us the code or alarm and what the generator is doing, and one of our engineers will help you diagnose it.
Search other controller alarms and engine fault codes, with troubleshooting steps, in Generator Oracle.
Launch Generator Oracle →Full diagnostic guide
A fault code names a symptom, not a cause. Our engineers have written the diagnostic sequence they use on site for this class of fault — ranked causes, ordered steps with the reading expected at each one, and the point at which to stop and call someone.
10 diagnostic steps · advanced · qualified electrician