EmersonEIMS — Reliable Power. Without Limits.
HOMEABOUTWHY US
INDUSTRIES
PHASE 4CONTACT
Get Quote

B2BEmersonEIMS serves commercial, industrial, healthcare, telecom, hospitality, government & contractor clients.• Engineering-led • SLA-backed • Documented commissioning

Talk to an engineerWhatsApp+254 768 860 665

Services Directory

View all services →

Power & Generators

  • Cummins Generators (3-yr warranty)
  • Generator Repairs & Maintenance
  • ATS / Changeovers
  • Generator Sales
  • Generator Rental
  • Generator Installation
  • Generator Spare Parts
  • Workshop Repairs & Fabrication
  • Power Interruption Solutions

Renewable & UPS

  • Solar Energy Solutions
  • Commercial / Industrial Solar
  • Solar System Sizing
  • Solar Genius Pro™
  • UPS Systems
  • UPS Lab
  • Solar / UPS Hub
  • Borehole Pumps

Electrical & HVAC

  • Distribution Boards & Panels
  • Motor Rewinding
  • Motors & Drives
  • High-Voltage Systems
  • Diesel Automation
  • Industrial Controls
  • Steel Fabrication
  • AC / HVAC Installation

Specialised & AI Suites

  • Hospital Incinerators
  • Incinerator Construction Guide
  • Building Engineering Suite
  • EIMS PRO Workspace
  • AquaScan Pro™
  • Generator Oracle™
  • Diagnostics Hub
  • Troubleshooting Wizard

Maintenance Hubs

  • Generator Maintenance
  • Solar Maintenance
  • HVAC Maintenance
  • Borehole Maintenance
  • Electrical Maintenance
  • Motors Maintenance
  • Incinerator Maintenance
  • Fabrication & Welding

Resources & Tools

  • Resources & Learning Hub
  • Knowledge Base
  • Technical Bible
  • Power Calculators
  • Fault Code Database
  • Blog & Articles
  • FAQ
  • Emergency Response Guide

Service Areas

  • All Kenya — 47 Counties
  • Nairobi
  • Mombasa
  • Kisumu
  • Nakuru
  • Kiambu
  • All Service Locations
EMERSONEiMS

Engineering-grade reliability for East Africa's critical infrastructure. Power systems built to perform.

  • LinkedIn↗
  • Twitter↗
  • Facebook↗

Company

  • About Us
  • All Services
  • Book a Service
  • Project Gallery
  • Case Studies
  • Industries Served
  • Careers
  • Contact Us

Quick Links

  • Generator Sales
  • Solar Energy
  • Diagnostic Suite
  • Solar / UPS Hub
  • Generator Oracle
  • Knowledge Base
  • FAQ

Contact

  • Nairobi HQEmbakasi, off Airport North Road, Nairobi
    (Near KEMSA Head Office)
  • Department Emails
    • General Inquiriesinfo@emersoneims.com
    • Service Coordinationemersoneimservices@emersoneims.com
    • Generator Deskgenerators@emersoneims.com
    • Solar & UPS Desksolar@emersoneims.com
    • Sally — Direct Accountsally@emersoneims.com
  • Phone
    +254782914717
    +254768860665

© 2026 Emerson EiMS. All rights reserved.

PROTECTED BY GENERATOR ORACLE / EMERSONEIMS
Privacy PolicyTerms of Service
ENGINEERED IN NAIROBI, KENYA
  1. Home
  2. /
  3. Repair Centre
  4. /
  5. generators
  6. /
  7. AVR Fault Diagnosis — Before You Replace the Regulator

Generating set alternators — excitation and voltage regulation

AVR Fault Diagnosis — Before You Replace the Regulator

Applies to
Brushless self-excited and PMG-excited alternators on diesel generating sets, single- and three-phase
Difficulty
advanced
Competence required
qualified electrician
Diagnosis complexity
Moderate. The AVR is the most frequently replaced component in the excitation chain and the least frequently at fault.
Electrical system
Set output 240 V / 415 V 50 Hz nominal; excitation from main output or a separate PMG
Safety classification
live electrical
Author
EmersonEIMS Engineering
Technical review
Mr. Kararaho
Last reviewed
2026-07-27

Scope — read this before relying on the guide

This guide sets out diagnostic method, ranked causes and safety requirements. It deliberately does not state equipment-specific numbers — test voltages, resistance and component values, torque figures, acceptance windows and pin assignments are referred to the manufacturer's documentation for your exact model rather than given here, because a plausible-looking figure for the wrong machine is more dangerous than no figure at all.

Direct technical answer

The AVR is the component most often replaced and least often responsible. Before condemning it, check three things that account for the majority of apparent AVR failures. First, the sensing fuses and sensing leads: an AVR that cannot see the output voltage behaves exactly like a failed regulator, and a blown sensing fuse costs almost nothing to check. Second, engine speed — every AVR includes an under-frequency protection that deliberately reduces excitation when speed falls below a set threshold, so a set running slow produces low voltage because the regulator is working correctly, and turning the voltage adjustment up to compensate causes dangerous over-excitation once normal speed returns. Third, the rest of the excitation chain, because the AVR is only one link: residual magnetism, exciter field and armature, and the rotating rectifier all sit between the regulator and the output. The definitive separation is to excite the machine independently by the manufacturer's documented procedure — if it then produces controlled voltage, the alternator is sound and the fault is in the regulator or its sensing; if it does not, the AVR was never the problem.

01Symptom description

Controller / display

  • ▪No voltage output with the engine running normally
  • ▪Output voltage low and not responding to the voltage adjustment
  • ▪Output voltage high, sometimes rising until protection operates
  • ▪Voltage unstable, hunting or drifting
  • ▪Under-frequency or excitation alarm on the controller

Indicators

  • ▪AVR fault or excitation indicator on regulators that provide one
  • ▪Excitation trip on the controller
  • ▪Voltmeter showing only residual voltage — a small output that will not build

Sounds

  • ▪Engine speed noticeably low or surging, which changes the diagnosis entirely
  • ▪Alternator noise change under load, which may indicate a rotating rectifier problem
  • ▪Load equipment behaving erratically as voltage wanders

Smells

  • ▪Burnt varnish or insulation smell from the alternator, indicating winding overheating
  • ▪Burnt smell from the AVR itself or its enclosure
  • ▪Any burnt smell means stop and investigate before further running

Behaviour

  • ▪Voltage low and frequency also low — this is a speed problem, not a regulation problem
  • ▪Voltage low while frequency is correct — now regulation is genuinely implicated
  • ▪Voltage builds then collapses under load, which suggests excitation capacity or a rotating rectifier fault
  • ▪Voltage rises uncontrolled, which is a serious condition requiring immediate shutdown
  • ▪Fault appeared after a load rejection, overload, or after the set was run in an unusual configuration
  • ▪A replacement AVR failed quickly, which almost always means the real fault was elsewhere

Visible

  • ▪Sensing fuse condition — check this first
  • ▪AVR condition: burnt components, swollen capacitors, corrosion, moisture
  • ▪Sensing and excitation lead terminations
  • ▪Rotating rectifier diodes and surge suppressor condition where accessible
  • ▪Evidence of winding overheating or insulation discolouration
  • ▪Voltage adjustment potentiometer position, and whether it has been tampered with

02What the fault means

In plain language

The Automatic Voltage Regulator keeps the generator output steady by adjusting how strongly the alternator is magnetised. When output voltage is wrong, the regulator gets the blame, but it can only regulate what it can measure and what the rest of the excitation system lets it control. Very often the regulator is doing exactly the right thing in response to a problem somewhere else, most commonly a blown sensing fuse or an engine running slow.

Technical explanation

In a brushless machine the AVR controls current into the stationary exciter field. That produces a rotating field in the exciter armature, whose output is rectified by the rotating rectifier assembly turning with the shaft, and the resulting DC feeds the main rotor field, which induces voltage in the main stator. The regulator senses output voltage and adjusts exciter field current to hold the setpoint. Two consequences follow. First, the AVR depends entirely on its sensing input: if sensing is lost through a blown fuse or an open lead, the regulator sees near-zero output and drives excitation to maximum, or shuts down, depending on design — either way behaving like a failure while functioning correctly. Second, every element downstream of the regulator can produce symptoms indistinguishable from regulator failure, and a failed rotating rectifier diode is the classic case: the machine produces reduced and often unstable output that collapses under load. AVRs also implement an under-frequency or volts-per-hertz characteristic which reduces the voltage setpoint proportionally below a threshold speed, protecting the machine from over-fluxing at low frequency. A set running below rated speed therefore produces low voltage as designed. Raising the voltage adjustment to correct that is a serious error, because at restored rated speed the machine is then over-excited, and sustained over-excitation overheats the windings.

03Common causes, ranked

These are ordered by likelihood. Presenting every possible cause as equally probable is a failure of diagnosis, not thoroughness.

Most likely

start here
  • ▪Sensing fuse blown or sensing lead open — the single most common cause of apparent AVR failure
  • ▪Engine speed low, so the AVR is correctly reducing voltage through under-frequency protection
  • ▪Loss of residual magnetism, so the machine cannot begin to build voltage
  • ▪Loose or corroded excitation or sensing terminations

Possible

check next
  • ▪Rotating rectifier diode failed, giving low or unstable output that collapses under load
  • ▪Voltage adjustment misadjusted or tampered with
  • ▪Exciter field winding open or shorted
  • ▪AVR itself failed

Less common

after the above
  • ▪Main rotor field winding fault
  • ▪Stator winding fault
  • ▪Surge suppressor on the rotating rectifier failed, taking diodes with it
  • ▪Controller or protection settings causing an excitation trip that is not an AVR fault at all
  • ▪Incorrect AVR fitted or configured for a different machine

Model specific

verify per unit
  • ▪AVR type, terminal designations, sensing arrangement and adjustment functions differ by manufacturer and model — take them from the alternator and AVR documentation for the machine in front of you
  • ▪Self-excited machines derive excitation from the main output; PMG-excited machines have an independent permanent magnet generator, and the diagnosis differs fundamentally between them
  • ▪Field flashing procedures are machine-specific and must never be applied to a PMG machine as a first step
  • ▪Under-frequency threshold and slope are configurable on many AVRs
  • ▪Stability and damping adjustments differ; adjusting them without understanding the machine can create instability

Environmental

site conditions
  • ▪Moisture and condensation in the alternator or AVR enclosure
  • ▪Dust ingress causing tracking across the AVR or terminals
  • ▪High ambient temperature reducing AVR and winding life
  • ▪Vibration loosening terminations over time

Installation related

built in
  • ▪AVR mounted where it is exposed to vibration or heat beyond its rating
  • ▪Sensing leads routed alongside power cables, picking up interference
  • ▪Incorrect AVR fitted during an earlier repair
  • ▪Load with a very poor power factor or high harmonic content beyond the machine design

Maintenance related

deferred work
  • ▪Sensing fuses never inspected
  • ▪Terminations never re-torqued
  • ▪Insulation resistance never tested, so a developing winding fault is unnoticed
  • ▪Voltage and frequency never recorded at service, so gradual drift is invisible

Component level

electronics
  • ▪Sensing fuse open
  • ▪Rotating rectifier diode failed open or short
  • ▪Surge suppressor failed
  • ▪Exciter field winding fault
  • ▪AVR output stage failed

04Safety requirements

Isolation

  • ▪A running generator produces lethal voltage at the alternator terminals and inside the terminal box
  • ▪Stop the set and prevent automatic restart before working in the terminal box or on the AVR
  • ▪Isolate the output breaker and prove dead at the point of work
  • ▪Isolate and lock the starting battery — a set in auto can start without warning

Lockout and tagout

  • ▪Lock the control selector in stop, and tag it
  • ▪Disconnect and tag the starting battery
  • ▪Lock and tag the output breaker
  • ▪Tag any changeover control so auto operation is not restored while work proceeds

PPE

  • ▪Arc-rated protection appropriate to the prospective fault energy at the alternator terminals
  • ▪Insulated tools rated for the system voltage
  • ▪Eye protection
  • ▪Hearing protection while the set is running

Stored energy

  • ▪Excitation circuits are inductive and can produce a substantial voltage when interrupted
  • ▪The starting battery remains live
  • ▪Rotating parts continue turning after shutdown

Specific hazards

  • ▪NEVER open-circuit a current transformer secondary while the machine is running and carrying load. A CT with an open secondary develops a dangerously high voltage across the break and can be lethal. Short CT secondaries before disturbing any connection in that circuit.
  • ▪Some diagnostic procedures require the set to be running with the terminal box open, which is live working — it must only be done by someone competent to do so, with the correct protection, or not at all
  • ▪Field flashing applies a source to the excitation circuit and must follow the manufacturer's documented procedure; never field-flash a PMG machine as a first step
  • ▪Uncontrolled over-voltage can damage connected equipment and injure people — shut down immediately rather than investigating a rising voltage while it runs
  • ▪Rotating rectifier inspection requires access to rotating parts; the set must be stopped and locked off

Stop and call a qualified professional if

  • ▪Output voltage is rising uncontrolled
  • ▪There is a burnt insulation smell from the alternator
  • ▪Diagnosis requires live working in the terminal box beyond your competence
  • ▪A winding fault is suspected
  • ▪A replacement AVR has already failed, indicating an unresolved fault elsewhere

05Tools required

Tools required and the reason each is needed
ToolWhy it is needed
True-RMS multimeter rated for the system voltageOutput, sensing and excitation measurements; a non-RMS meter misreads distorted waveforms
Frequency meter or a multimeter that reads frequency reliablyEstablishing whether the fault is speed or regulation — the first fork in the diagnosis
Clamp meterExcitation current, and load current when assessing behaviour under load
Insulation resistance testerTesting exciter and main windings where a winding fault is suspected
Diode test capability on the multimeterChecking rotating rectifier diodes, a common cause misattributed to the AVR
Alternator and AVR documentation for the specific machineTerminal designations, sensing arrangement and field-flashing procedure must be read, never assumed
Insulated tools and arc-rated protectionWork in and around an alternator terminal box

06Diagnostic decision tree

Diagnostic decision flowchart: AVR Fault Diagnosis — Before You Replace the RegulatorA 7-step decision flowchart. Each step asks a diagnostic question; answering yes continues down to the next question, while answering no leads to the stated finding. The same sequence is written out in full immediately below this diagram.1. Is output voltage rising uncontrolled?Yes — Shut down immediately. Do not investigate whilerunning.NoContinueYes2. Is there a burnt insulation smell from thealternator?Yes — Stop and escalate — suspect a winding faultNoContinueYes3. Are voltage AND frequency both low together?Yes — This is an engine speed problem. Correct speed first —the AVR is behaving correctly.NoContinueYes4. Are the sensing fuses intact and the sensing leadscontinuous?Yes — ContinueNoThat explains it. An AVR that cannotsense output behaves exactly like afailed one.Yes5. Does the machine produce any residual voltage at all?Yes — ContinueNoResidual magnetism may be lost —field-flash by the manufacturerprocedure, and never on a PMG machineas a first stepYes6. Do the rotating rectifier diodes test healthy?Yes — ContinueNoA failed diode produces low, unstableoutput that collapses under load, andis routinely blamed on the AVRYes7. With independent excitation applied per themanufacturer procedure, does the machine producecontrolled voltage?Yes — The alternator is sound — the fault is the AVR or itssensingNoThe alternator itself is at fault; theAVR was never the problemYesContinue to the step-by-step diagnosis below.
Diagnostic decision flow for avr fault diagnosis — before you replace the regulator. Simplified illustration — not a replacement for the manufacturer's model-specific schematic or service data. The same sequence is written out in full below.
  1. 1. Is output voltage rising uncontrolled?

    Yes → Shut down immediately. Do not investigate while running.

    No → Continue

  2. 2. Is there a burnt insulation smell from the alternator?

    Yes → Stop and escalate — suspect a winding fault

    No → Continue

  3. 3. Are voltage AND frequency both low together?

    Yes → This is an engine speed problem. Correct speed first — the AVR is behaving correctly.

    No → Continue

  4. 4. Are the sensing fuses intact and the sensing leads continuous?

    Yes → Continue

    No → That explains it. An AVR that cannot sense output behaves exactly like a failed one.

  5. 5. Does the machine produce any residual voltage at all?

    Yes → Continue

    No → Residual magnetism may be lost — field-flash by the manufacturer procedure, and never on a PMG machine as a first step

  6. 6. Do the rotating rectifier diodes test healthy?

    Yes → Continue

    No → A failed diode produces low, unstable output that collapses under load, and is routinely blamed on the AVR

  7. 7. With independent excitation applied per the manufacturer procedure, does the machine produce controlled voltage?

    Yes → The alternator is sound — the fault is the AVR or its sensing

    No → The alternator itself is at fault; the AVR was never the problem

07Step-by-step diagnosis

Step 1Measure voltage and frequency together

Inspect
Output voltage and frequency at the same instant
Where
Alternator output terminals or the control panel instruments
Instrument
True-RMS multimeter with frequency capability
Expected result
Both at nominal
If the result is abnormal
Both low together is an engine speed problem and the AVR is correctly reducing voltage through its under-frequency protection. Voltage low with correct frequency puts regulation genuinely in question. This single comparison redirects most of these jobs.
Next
Step 2

Safety: Never raise the voltage adjustment to compensate for low speed. At restored speed the machine is then over-excited and the windings overheat.

Step 2Check the sensing fuses and leads

Inspect
Sensing fuse continuity and the integrity of sensing leads to the AVR
Where
AVR sensing circuit, set stopped and isolated
Instrument
Multimeter on continuity
Expected result
Fuses intact, leads continuous and terminations tight
If the result is abnormal
This is the most common cause of apparent AVR failure and the cheapest to check. Establish why a fuse blew rather than simply replacing it.
Next
Step 3

Verify for your unit: Which fuses are the sensing fuses on this specific machine — designations differ between manufacturers.

Step 3Inspect the AVR and its environment

Inspect
AVR for burnt components, swollen capacitors, moisture, dust tracking and secure terminations
Where
At the AVR, set stopped and isolated
Instrument
Inspection light and magnification
Expected result
Clean, dry, undamaged, all terminations tight
If the result is abnormal
Moisture and dust tracking cause erratic regulation that comes and goes with weather. Note the voltage adjustment position before touching it.
Next
Step 4

Step 4Establish whether residual voltage is present

Inspect
Whether the machine produces any small output at all when run
Where
Output terminals
Instrument
True-RMS multimeter
Expected result
Some residual voltage present, from which the machine can build
If the result is abnormal
No residual at all suggests lost residual magnetism. Field-flash strictly by the manufacturer's documented procedure for this machine.
Next
Step 5

Safety: Never field-flash a PMG-excited machine as a first step — the diagnosis for those machines is fundamentally different.

Step 5Test the rotating rectifier

Inspect
Each diode in the rotating rectifier assembly, and the surge suppressor
Where
On the rotating assembly, set stopped and locked off
Instrument
Multimeter on diode test
Expected result
Each diode conducting in one direction only, all consistent with each other
If the result is abnormal
A failed diode gives reduced and often unstable output that collapses under load — symptoms routinely attributed to the AVR. Comparative testing across the diodes is valid without any absolute figure.
Next
Step 6

Safety: The set must be stopped and locked off; this work is on rotating parts.

Step 6Test the exciter and main windings

Inspect
Winding continuity and insulation resistance
Where
Exciter field, exciter armature and main windings as accessible
Instrument
Multimeter and insulation resistance tester
Expected result
Continuity as expected and insulation resistance healthy
If the result is abnormal
A winding fault changes the job from regulator replacement to alternator repair. Take acceptance values from the machine documentation rather than a general figure.
Next
Step 7

Verify for your unit: Winding resistance and insulation acceptance values for this specific alternator, from the manufacturer data.

Step 7Separate the AVR from the alternator by independent excitation

Inspect
Whether the machine produces controlled output when excited independently of the AVR
Where
Per the manufacturer's documented separate-excitation procedure
Instrument
As specified by the manufacturer for this machine
Expected result
Controlled voltage produced, proving the alternator sound
If the result is abnormal
This is the definitive separation. Voltage produced means the alternator is healthy and the fault is the AVR or its sensing; no voltage means the alternator is at fault and replacing the AVR would have achieved nothing.
Next
Step 8

Safety: Follow the manufacturer procedure exactly. Improvised excitation can damage windings and is dangerous.

Step 8Only now replace the AVR, and confirm the cause

Inspect
Correct AVR type and configuration for the machine, and the reason the original failed
Where
At the AVR
Instrument
Machine documentation
Expected result
Correct part, correctly configured, with the original failure explained
If the result is abnormal
A replacement AVR that fails quickly means the real fault was never found. Do not fit a second one without investigating further.
Next
Proceed to validation under load

08Repair procedure

Sensing and terminations

cleaning and connections
  • ▪Replace blown sensing fuses with the correct type and rating, having established why they operated
  • ▪Repair or replace open or damaged sensing leads and re-route them away from power cables
  • ▪Clean and re-torque all excitation and sensing terminations
  • ▪Dry out and protect the AVR enclosure where moisture ingress is evident

This resolves a large proportion of jobs booked as AVR failures.

Speed and adjustment

configuration
  • ▪Correct engine speed to rated before making any voltage adjustment
  • ▪Set voltage to nominal at rated speed, using the adjustment as designed rather than to mask another fault
  • ▪Verify stability settings are appropriate to the machine before altering them

Setting voltage correct at low speed guarantees over-excitation at rated speed. Speed first, always.

Excitation chain components

component replacement
  • ▪Replace failed rotating rectifier diodes as a complete set, together with the surge suppressor
  • ▪Replace the AVR only with the correct type for the machine, correctly configured
  • ▪Do not fit a substitute AVR of a different type without confirming compatibility with the excitation system

Alternator repair

manufacturer level
  • ▪Refer exciter and main winding faults for specialist alternator repair or rewind
  • ▪Provide the measurements, insulation test results and the separate-excitation result

09Post-repair validation

  • ▪Confirm rated speed and frequency before assessing voltage
  • ▪Confirm output voltage at nominal, balanced across phases, at no load
  • ▪Apply load progressively and confirm voltage holds within limits through load steps
  • ▪Confirm voltage recovery after a load step is prompt and without hunting
  • ▪Measure excitation current under load and confirm it is stable
  • ▪Thermally check the alternator and AVR after a sustained run
  • ▪Confirm no burnt smell or abnormal noise develops under sustained load
  • ▪Record voltage, frequency, load and excitation readings in the maintenance record

10When not to repair

  • ▪Alternator windings with failed insulation, where rewind or replacement is the correct route
  • ▪Repeated AVR failure after replacement, which indicates an unresolved fault in the excitation chain or the load
  • ▪Obsolete alternators where AVRs and rotating rectifier components are unobtainable
  • ▪Machines that have been run over-excited long enough to damage insulation
  • ▪Where a substitute AVR of unknown compatibility is the only option — the risk of over-excitation is not worth it

11Prevention

  • ▪Inspect sensing fuses at every service — they are trivial to check and a leading cause
  • ▪Record voltage, frequency and excitation current at each service so drift is visible
  • ▪Test insulation resistance periodically to catch a developing winding fault early
  • ▪Keep the terminal box and AVR enclosure sealed against moisture and dust
  • ▪Re-torque excitation and sensing terminations at service intervals
  • ▪Correct engine speed problems promptly, since running below rated speed stresses the whole excitation system
  • ▪Record the voltage adjustment position at commissioning so tampering is detectable

12Questions engineers actually ask

The output voltage is low. Can I just turn the AVR adjustment up?

Not until you have checked frequency. If frequency is also low the engine is running slow, and the AVR is reducing voltage deliberately through its under-frequency protection. Turning the adjustment up masks that, and when the speed is restored the machine is over-excited, which overheats the windings. Fix the speed first, then set voltage at rated speed.

I fitted a new AVR and it failed within days. Why?

Because the AVR was almost certainly not the original fault. The commonest reasons are a fault elsewhere in the excitation chain — a failed rotating rectifier diode is the classic — or a sensing problem, or a machine being run at incorrect speed. Fitting a second AVR without finding the underlying cause usually destroys that one too.

How do I know whether it is the AVR or the alternator?

Excite the machine independently of the AVR using the manufacturer's documented procedure for that alternator. If it then produces controlled voltage, the alternator and its excitation chain are sound and the fault is the regulator or its sensing. If it does not, the alternator is at fault and the AVR was never the problem. That test settles the question definitively.

Is it safe to work in the terminal box while the set is running?

It is live working and carries real risk, including arc flash. Some diagnostic steps genuinely require the machine to be running, and those must be done only by someone competent with the correct protection — or not at all. One rule is absolute: never open-circuit a current transformer secondary while the machine is carrying load, because the voltage that develops across the break can be lethal.

Standards and references

  • ▪IEC 60034-1 — rotating electrical machines: rating and performance
  • ▪ISO 8528-1 and ISO 8528-5 — generating sets: application, ratings and performance, including voltage regulation classes
  • ▪IEEE 115 — test procedures for synchronous machines
  • ▪The alternator and AVR manufacturer's documentation for the specific machine, which is the only valid source for terminal designations, winding values, field-flashing and separate-excitation procedures referred to throughout

This guidance is written from engineering principle and is not a substitute for the manufacturer's model-specific documentation. Where a figure is model-specific, confirm it against the service data for your unit before acting on it.

Need this diagnosed properly?

Send us the make, model and any fault codes shown, and photographs of the controller display if you have them. Our mobile workshop covers all 47 counties.

Call 0768860665WhatsApp the fault detailsRequest a site inspection

Related diagnosis guides

  • generator produces no voltage output
  • generator unstable voltage