Skip to main contentSkip to navigationSkip to contactAccessibility (Alt+A)

Keyboard Shortcuts

  • Alt + A: Open accessibility settings
  • Tab: Navigate to next element
  • Shift + Tab: Navigate to previous element
  • Enter or Space: Activate buttons and links
  • Escape: Close dialogs and menus
  • Arrow keys: Navigate within menus and sliders
  • Home: Go to beginning of list
  • End: Go to end of list
EmersonEIMS — Reliable Power. Without Limits.
HOMEABOUTWHY US
INDUSTRIES
PHASE 4CONTACT
Get Quote

B2BEmersonEIMS serves commercial, industrial, healthcare, telecom, hospitality, government & contractor clients.• Engineering-led • SLA-backed • Documented commissioning

Talk to an engineerWhatsApp+254 768 860 665

Services Directory

View all services →

Power & Generators

  • Cummins Generators (3-yr warranty)
  • Generator Repairs & Maintenance
  • ATS / Changeovers
  • Generator Sales
  • Generator Rental
  • Generator Installation
  • Generator Spare Parts
  • Workshop Repairs & Fabrication
  • Power Interruption Solutions

Renewable & UPS

  • Solar Energy Solutions
  • Commercial / Industrial Solar
  • Solar System Sizing
  • Solar Genius Pro™
  • UPS Systems
  • UPS Lab
  • Solar / UPS Hub
  • Borehole Pumps

Electrical & HVAC

  • Distribution Boards & Panels
  • Motor Rewinding
  • Motors & Drives
  • High-Voltage Systems
  • Diesel Automation
  • Industrial Controls
  • Steel Fabrication
  • AC / HVAC Installation

Specialised & AI Suites

  • Hospital Incinerators
  • Incinerator Construction Guide
  • Building Engineering Suite
  • EIMS PRO Workspace
  • AquaScan Pro™
  • Generator Oracle™
  • Diagnostics Hub
  • Troubleshooting Wizard

Maintenance Hubs

  • Generator Maintenance
  • Solar Maintenance
  • HVAC Maintenance
  • Borehole Maintenance
  • Electrical Maintenance
  • Motors Maintenance
  • Incinerator Maintenance
  • Fabrication & Welding

Resources & Tools

  • Resources & Learning Hub
  • Knowledge Base
  • Technical Bible
  • Power Calculators
  • Fault Code Database
  • Blog & Articles
  • FAQ
  • Emergency Response Guide

Service Areas

  • All Kenya — 47 Counties
  • Nairobi
  • Mombasa
  • Kisumu
  • Nakuru
  • Kiambu
  • All Service Locations
EMERSONEiMS

Engineering-grade reliability for East Africa's critical infrastructure. Power systems built to perform.

  • LinkedIn↗
  • Twitter↗
  • Facebook↗

Company

  • About Us
  • All Services
  • Book a Service
  • Project Gallery
  • Case Studies
  • Industries Served
  • Careers
  • Contact Us

Quick Links

  • Generator Sales
  • Solar Energy
  • Diagnostic Suite
  • Solar / UPS Hub
  • Generator Oracle
  • Knowledge Base
  • FAQ

Contact

  • Nairobi HQEmbakasi, off Airport North Road, Nairobi
    (Near KEMSA Head Office)
  • Department Emails
    • General Inquiriesinfo@emersoneims.com
    • Service Coordinationemersoneimservices@emersoneims.com
    • Generator Deskgenerators@emersoneims.com
    • Solar & UPS Desksolar@emersoneims.com
    • Sally — Direct Accountsally@emersoneims.com
  • Phone
    +254782914717
    +254768860665

© 2026 Emerson EiMS. All rights reserved.

PROTECTED BY GENERATOR ORACLE / EMERSONEIMS
Privacy PolicyTerms of Service
ENGINEERED IN NAIROBI, KENYA
  1. Home
  2. /
  3. Repair Centre
  4. /
  5. ups
  6. /
  7. Online UPS Bypass Fault — Diagnosis and Repair

Online double-conversion UPS — static bypass and transfer

Online UPS Bypass Fault — Diagnosis and Repair

Applies to
Online double-conversion UPS systems with static bypass, single- and three-phase, including modular and parallel installations
Difficulty
advanced
Competence required
qualified electrician
Diagnosis complexity
Moderate, but the consequence is severe: a bypass fault removes the protection that catches an inverter failure.
Electrical system
Bypass supply 240 V / 415 V 50 Hz nominal; DC bus per UPS design
Safety classification
multiple hazard
Author
EmersonEIMS Engineering
Technical review
Mr. Kararaho
Last reviewed
2026-07-27

Scope — read this before relying on the guide

This guide sets out diagnostic method, ranked causes and safety requirements. It deliberately does not state equipment-specific numbers — test voltages, resistance and component values, torque figures, acceptance windows and pin assignments are referred to the manufacturer's documentation for your exact model rather than given here, because a plausible-looking figure for the wrong machine is more dangerous than no figure at all.

Direct technical answer

Treat a bypass fault as urgent even though the load is still running, because the bypass is the safety net that catches an inverter failure or an overload — without it the next fault drops the load. Diagnosis turns on one question: is the bypass supply itself unacceptable, or is the transfer path unable to use it? Measure the bypass supply at the UPS bypass input, checking frequency and phase rotation as well as voltage, because a bypass source outside the acceptance window is rejected exactly as a rectifier input would be. The second and less obvious cause is synchronisation. For a break-free transfer the inverter must remain synchronised with the bypass source, so if the bypass frequency wanders — most commonly when the site is running on a generator — the UPS cannot hold sync and will declare bypass unavailable while both supplies individually look healthy. Only when supply and synchronisation are proven should the static switch itself be suspected. Note also that a maintenance bypass and a static bypass are different things with different failure modes; establish which one the alarm concerns before investigating.

01Symptom description

Controller / display

  • ▪Bypass unavailable, bypass fault or bypass out of tolerance
  • ▪Loss of synchronisation, or inverter not synchronised with bypass
  • ▪Static switch fault
  • ▪Bypass frequency or phase rotation error
  • ▪Load on inverter with bypass unavailable — the condition that matters most

Indicators

  • ▪Bypass path indicator dark on the mimic display while the inverter path is healthy
  • ▪Alarm active with the load still supplied normally
  • ▪Bypass input breaker open

Sounds

  • ▪Audible alarm with no change in load behaviour
  • ▪Static switch or contactor operating repeatedly as the unit attempts and abandons synchronisation
  • ▪Cooling fans running harder, which may accompany a static switch problem

Smells

  • ▪Burnt smell from the bypass section or static switch assembly — stop and investigate before any transfer attempt
  • ▪Hot insulation smell around bypass terminations, indicating a loose or overloaded joint

Behaviour

  • ▪Bypass unavailable only while the site runs on generator, which is a synchronisation problem rather than a UPS fault
  • ▪Bypass alarm appearing and clearing through the day as supply quality varies
  • ▪Bypass lost after upstream electrical work, which frequently means phase rotation was reversed
  • ▪Load transferred to bypass and would not transfer back
  • ▪Unit refuses to transfer for a planned maintenance operation

Visible

  • ▪Bypass input breaker and fuse condition
  • ▪Maintenance bypass switch position — it is often found in the wrong position after earlier work
  • ▪Bypass terminations for heat discolouration or looseness
  • ▪Phase rotation indication where provided
  • ▪Evidence of recent upstream changes to the installation

02What the fault means

In plain language

The UPS has a second path that can feed the load directly from the incoming supply, used when the UPS is overloaded, has an internal fault, or needs maintenance. A bypass fault means that path is not available. The load is usually still running normally, which is why this gets ignored, but if anything then goes wrong with the main path, there is nothing to catch it.

Technical explanation

An online double-conversion UPS supplies the load continuously through rectifier and inverter, with a static bypass providing an alternative path directly from the bypass supply. The static switch can transfer the load between inverter and bypass, and for that transfer to occur without a break in supply the inverter output must be synchronised in frequency and phase with the bypass source. The UPS therefore tracks the bypass source continuously and only permits transfer while synchronised and while the bypass supply satisfies its acceptance criteria for voltage, frequency and, on three-phase units, phase rotation. Two independent conditions can therefore remove bypass availability: an unacceptable bypass supply, or a supply that is acceptable but which the inverter cannot lock to. The second is common on generator-backed sites, because engine-driven sets exhibit frequency excursions during load steps that exceed the rate the inverter is permitted to follow — the UPS then reports bypass unavailable while both the inverter and the generator are individually healthy. Because the bypass path is the protection of last resort, its loss does not interrupt the load but removes the response to any subsequent inverter fault, overload or short circuit, which is why it is an urgent condition despite being invisible to users. The maintenance bypass is a separate, manually operated path used to isolate the UPS entirely for service; it is mechanically interlocked in most designs and its failure modes are unrelated to the static bypass.

03Common causes, ranked

These are ordered by likelihood. Presenting every possible cause as equally probable is a failure of diagnosis, not thoroughness.

Most likely

start here
  • ▪Bypass supply outside the acceptance window — commonly frequency, on generator supply
  • ▪Inverter unable to synchronise with a wandering bypass frequency
  • ▪Bypass input breaker open or fuse blown
  • ▪Phase rotation reversed after upstream electrical work

Possible

check next
  • ▪Maintenance bypass switch left in the wrong position after earlier work
  • ▪Bypass acceptance window configured too narrowly for the site supply
  • ▪Loose or high-resistance bypass termination
  • ▪Lost phase on a three-phase bypass supply

Less common

after the above
  • ▪Static switch device failure
  • ▪Synchronisation or phase-locked control circuit failure
  • ▪Bypass sensing circuit failure
  • ▪Control or logic board fault reporting a condition that does not exist
  • ▪Interlock or auxiliary contact failure on the bypass path

Model specific

verify per unit
  • ▪Bypass acceptance windows for voltage, frequency and slew rate are configurable and model-specific — read them from the unit
  • ▪Some units offer a wider bypass window or generator mode intended for engine-driven supplies
  • ▪Transfer behaviour, and whether an unsynchronised transfer is permitted at all, differs by model
  • ▪Maintenance bypass interlocking arrangements differ; some are mechanical, some electrical
  • ▪Parallel and modular systems have additional synchronisation requirements between modules

Environmental

site conditions
  • ▪Generator supply with frequency instability
  • ▪Weak or unstable utility supply
  • ▪High ambient temperature affecting the static switch assembly
  • ▪Dust or humidity causing tracking on bypass circuitry

Installation related

built in
  • ▪Bypass supply taken from a source with poorer quality than the rectifier input
  • ▪Generator sized without regard to the UPS load characteristic
  • ▪Bypass cabling undersized, causing voltage drop under transferred load
  • ▪Phase rotation not verified after installation or alteration

Maintenance related

deferred work
  • ▪Bypass path never exercised, so a failure is discovered only when it is needed
  • ▪Bypass acceptance settings never reviewed against the real site supply
  • ▪Bypass terminations never re-torqued or thermally surveyed
  • ▪Maintenance bypass operation never practised, so it is performed incorrectly under pressure

Component level

electronics
  • ▪Static switch device failed
  • ▪Bypass fuse open
  • ▪Synchronisation control circuit failed
  • ▪Bypass voltage or frequency sensing failed
  • ▪Auxiliary contact or interlock failed

04Safety requirements

Isolation

  • ▪A UPS has multiple independent sources — rectifier input, bypass input, battery and inverter output. Isolating one does not make the unit safe.
  • ▪The bypass input can be live even when the rectifier input is isolated, because it is frequently a separate feed
  • ▪Isolate every source and prove dead at the point of work
  • ▪Confirm the DC bus has discharged before opening the enclosure

Lockout and tagout

  • ▪Lock and tag the rectifier input, the bypass input, the battery isolator and the maintenance bypass
  • ▪Confirm explicitly with the site that the load may lose protection during the work
  • ▪Where the maintenance bypass is used to carry the load, verify it is actually carrying it before isolating the UPS
  • ▪Keep the only key with the person doing the work

PPE

  • ▪Arc-rated protection appropriate to the prospective fault energy at the bypass input
  • ▪Insulated tools rated for the system voltage
  • ▪Eye protection

Stored energy

  • ▪The DC bus and battery string remain at dangerous voltage after shutdown
  • ▪Observe and verify the manufacturer's capacitor discharge period rather than trusting elapsed time
  • ▪The battery string cannot be switched off

Specific hazards

  • ▪BACKFEED: a UPS can energise terminals that appear isolated. Always prove dead at the point of work immediately before starting, never on the basis of an upstream isolation alone.
  • ▪Operating the maintenance bypass incorrectly can drop the load instantly. Know the correct sequence for the specific unit before touching it, and never improvise the order.
  • ▪An unsynchronised transfer can subject the load to a break or a phase step. Do not force a transfer to clear an alarm.
  • ▪Never open-circuit a current transformer secondary while the machine carries load
  • ▪Working on a live bypass supply is live working and must be treated as such

Stop and call a qualified professional if

  • ▪There is a burnt smell or visible damage in the bypass or static switch section
  • ▪The maintenance bypass sequence for this unit is not documented or not understood
  • ▪The load cannot lose protection and no alternative arrangement exists
  • ▪Static switch or synchronisation control failure is suspected
  • ▪The unit is part of a parallel or modular system whose transfer logic you are not familiar with

05Tools required

Tools required and the reason each is needed
ToolWhy it is needed
True-RMS multimeter rated for the system voltageBypass supply voltage measured at the UPS bypass input, not at a nearby board
Frequency meter or power quality analyser with loggingBypass frequency and its stability — the leading cause, and one a spot reading will miss
Phase rotation testerReversed rotation after upstream works is a classic and instantly disqualifies the bypass
Clamp meterConfirming load path and current during and after transfer
Thermal cameraBypass terminations and static switch assembly under load
Insulated torque wrenchBypass terminations must be torqued to specification
UPS service interface and event logThe log usually states precisely why bypass was declared unavailable, which is faster than inferring it
Unit documentation for the maintenance bypass sequenceThe correct order is unit-specific and an error drops the load

06Diagnostic decision tree

Diagnostic decision flowchart: Online UPS Bypass Fault — Diagnosis and RepairA 8-step decision flowchart. Each step asks a diagnostic question; answering yes continues down to the next question, while answering no leads to the stated finding. The same sequence is written out in full immediately below this diagram.1. Is there a burnt smell or visible damage in thebypass section?Yes — Stop. Do not attempt a transfer. Escalate.NoContinueYes2. Does the alarm concern the STATIC bypass or theMAINTENANCE bypass?Yes — Identify which before proceeding — they are differentpaths with different failure modesNoRead the event log to establish whichYes3. Is the maintenance bypass switch in its correctnormal position?Yes — ContinueNoThat explains it — it is frequentlyleft wrong after earlier workYes4. Is the bypass input breaker closed and fuse intact?Yes — ContinueNoEstablish why it opened beforerestoring itYes5. Is bypass supply present at the UPS bypass input, allphases, correct rotation?Yes — ContinueNoThe problem is the supply or itsrotation, not the UPSYes6. Is bypass frequency within the acceptance window andstable?Yes — ContinueNoFrequency instability — usuallygenerator governing. The UPS isbehaving correctly.Yes7. Is the site running on a generator when the faultappears?Yes — Synchronisation with a wandering source is the likelycause; address the set, not the UPSNoContinueYes8. With a proven-good, stable, correctly rotated bypasssupply, is bypass still unavailable?Yes — Static switch or synchronisation control — refer forspecialist diagnosisNoResolved; validate and recordYesContinue to the step-by-step diagnosis below.
Diagnostic decision flow for online ups bypass fault — diagnosis and repair. Simplified illustration — not a replacement for the manufacturer's model-specific schematic or service data. The same sequence is written out in full below.
  1. 1. Is there a burnt smell or visible damage in the bypass section?

    Yes → Stop. Do not attempt a transfer. Escalate.

    No → Continue

  2. 2. Does the alarm concern the STATIC bypass or the MAINTENANCE bypass?

    Yes → Identify which before proceeding — they are different paths with different failure modes

    No → Read the event log to establish which

  3. 3. Is the maintenance bypass switch in its correct normal position?

    Yes → Continue

    No → That explains it — it is frequently left wrong after earlier work

  4. 4. Is the bypass input breaker closed and fuse intact?

    Yes → Continue

    No → Establish why it opened before restoring it

  5. 5. Is bypass supply present at the UPS bypass input, all phases, correct rotation?

    Yes → Continue

    No → The problem is the supply or its rotation, not the UPS

  6. 6. Is bypass frequency within the acceptance window and stable?

    Yes → Continue

    No → Frequency instability — usually generator governing. The UPS is behaving correctly.

  7. 7. Is the site running on a generator when the fault appears?

    Yes → Synchronisation with a wandering source is the likely cause; address the set, not the UPS

    No → Continue

  8. 8. With a proven-good, stable, correctly rotated bypass supply, is bypass still unavailable?

    Yes → Static switch or synchronisation control — refer for specialist diagnosis

    No → Resolved; validate and record

07Step-by-step diagnosis

Step 1Establish the risk before diagnosing

Inspect
Whether the load is currently protected, and what happens if the inverter path fails now
Where
UPS mimic display and site load schedule
Instrument
UPS display
Expected result
A conscious decision about the load before work begins
If the result is abnormal
A bypass fault leaves the load with no fallback. Where the load is critical, arrange an alternative before investigating rather than after.
Next
Step 2

Step 2Read the event log

Inspect
The stated reason bypass was declared unavailable, and whether it recurs
Where
UPS service interface
Instrument
Service interface
Expected result
A specific reason — frequency, voltage, rotation, sync loss or static switch
If the result is abnormal
A pattern tied to generator running hours points immediately at synchronisation rather than a component fault.
Next
Step 3

Step 3Confirm which bypass path is involved and check switch positions

Inspect
Static bypass versus maintenance bypass, and the maintenance bypass switch position
Where
At the UPS and its maintenance bypass panel
Instrument
Visual inspection against the unit documentation
Expected result
Maintenance bypass in its correct normal position, interlocks intact
If the result is abnormal
A maintenance bypass left in the wrong position after earlier work is a common and immediately explanatory finding.
Next
Step 4

Safety: Do not operate the maintenance bypass to test it without knowing the correct sequence for this unit — an error drops the load.

Step 4Measure the bypass supply at the UPS bypass input

Inspect
Voltage on every phase at the bypass input terminals
Where
UPS bypass input terminals
Instrument
True-RMS multimeter
Expected result
Nominal voltage, balanced, all phases present
If the result is abnormal
A lost phase is easy to miss and disqualifies the bypass entirely. Measure at the UPS, not at a nearby distribution board.
Next
Step 5

Step 5Check bypass frequency and stability

Inspect
Frequency and how much it moves, especially through load changes
Where
Bypass input terminals
Instrument
Frequency meter or logging analyser
Expected result
Frequency at nominal and steady enough for the inverter to track
If the result is abnormal
This is the leading cause. A generator whose frequency wanders on load steps prevents synchronisation, and the UPS correctly declares bypass unavailable while both supplies look individually healthy.
Next
Step 6

Verify for your unit: The configured bypass acceptance window and permitted slew rate for this model — these are model-specific and must be read from the unit.

Step 6Verify phase rotation

Inspect
Rotation of the bypass supply against the unit requirement
Where
Bypass input terminals
Instrument
Phase rotation tester
Expected result
Correct rotation
If the result is abnormal
Reversed rotation disqualifies bypass outright and is a classic consequence of upstream electrical work or a generator connection made in haste.
Next
Step 7

Step 7Inspect and thermally survey the bypass path

Inspect
Terminations, static switch assembly and busbars under load
Where
Bypass path through the unit
Instrument
Thermal camera, insulated torque wrench
Expected result
All connections cool and correctly torqued
If the result is abnormal
A high-resistance joint causes voltage collapse when the bypass is loaded, producing a fault that only appears at the moment it matters.
Next
Step 8

Step 8Only then suspect the static switch or synchronisation control

Inspect
Static switch condition and the unit's reported synchronisation state with a proven-good supply
Where
Within the unit
Instrument
Service interface, with all supply causes eliminated
Expected result
A supply proven acceptable and stable, with the unit still refusing bypass
If the result is abnormal
Only at this point is an internal fault the likely answer. Refer for specialist diagnosis with the supply measurements recorded.
Next
Refer to the manufacturer or a properly equipped specialist

08Repair procedure

Bypass path integrity

cleaning and connections
  • ▪Re-torque bypass terminations to specification and re-survey thermally under load
  • ▪Replace overheated or damaged bypass conductors
  • ▪Restore a lost phase at its source rather than at the UPS

Acceptance and synchronisation settings

configuration
  • ▪Compare the configured bypass window against the supply the site actually has, measured over time
  • ▪Where the unit provides a generator or wide-bypass mode, enable it deliberately and within manufacturer limits
  • ▪Correct phase rotation at the source
  • ▪Re-verify after any firmware or configuration change

Widening the window is legitimate where measurement shows the supply is genuinely acceptable but marginal. Widening it to silence an alarm defeats the purpose of the bypass.

Generator side

mechanical
  • ▪Correct governing so frequency holds through load steps and the inverter can track it
  • ▪Review generator sizing against the UPS load characteristic
  • ▪Review transfer switch timing so the supply is presented only once the set has stabilised

Where the fault only appears on generator, this is the repair.

Bypass components

component replacement
  • ▪Replace open bypass fuses after establishing why they operated
  • ▪Replace failed interlocks and auxiliary contacts

Static switch and control

manufacturer level
  • ▪Refer static switch and synchronisation control faults to the manufacturer or a properly equipped specialist
  • ▪Provide the measured bypass voltages, frequencies, rotation and the event log

09Post-repair validation

  • ▪Confirm the unit reports bypass available and synchronised
  • ▪Confirm bypass supply voltage, frequency and rotation measured at the UPS input
  • ▪Where the site has a generator, verify bypass remains available with the set running under real load — not only on utility
  • ▪Exercise a transfer to bypass and back, at a planned time, following the documented sequence
  • ▪Thermally survey the bypass path under transferred load
  • ▪Confirm the maintenance bypass is returned to its correct normal position and interlocks are intact
  • ▪Review the event log after a settling period to confirm the alarms have stopped rather than become less frequent
  • ▪Record all measurements and any settings changed, with the justification

10When not to repair

  • ▪Where the real fault is generator governing or sizing — no UPS work will resolve it
  • ▪Obsolete units where static switch assemblies and control boards are unobtainable
  • ▪Where the only way to restore bypass availability is to widen the window so far that unacceptable power could reach the load
  • ▪Where the bypass supply arrangement requires redesign rather than repair

11Prevention

  • ▪Exercise the bypass path at planned intervals — a path never tested is discovered failed at the worst moment
  • ▪Practise the maintenance bypass sequence with the documentation before it is needed under pressure
  • ▪Verify bypass availability with the site running on generator, not only on utility
  • ▪Record commissioned bypass voltage, frequency and rotation so later drift is detectable
  • ▪Review UPS event logs at every service visit; intermittent bypass alarms are an early warning
  • ▪Verify phase rotation after any upstream electrical work as a matter of routine
  • ▪Thermally survey bypass terminations annually under load

12Questions engineers actually ask

The load is running fine. Why does a bypass fault matter?

Because the bypass is what catches the next problem. With bypass unavailable, an inverter fault, an overload or a downstream short circuit has nowhere to transfer the load to, and it drops. The load running normally today is exactly why this alarm gets ignored until the day it costs an outage.

Bypass is unavailable only when we are on the generator. Is the UPS faulty?

Almost certainly not. For a break-free transfer the inverter must stay synchronised with the bypass source, and a generator whose frequency moves during load steps cannot be tracked within the permitted limits. The UPS is protecting the load by refusing an unsynchronised transfer. The fix is on the generator — governing and sizing — not in the UPS.

Can I just widen the bypass acceptance window to clear the alarm?

Only if measurement shows the supply is genuinely acceptable and merely sits outside a conservatively set window. Widening it so that genuinely poor power could be passed straight to the load removes the reason the bypass has criteria at all. Measure first, change deliberately within manufacturer limits, and record why.

Is the maintenance bypass the same as the static bypass?

No, and confusing them wastes time. The static bypass is an automatic electronic path the UPS uses to transfer the load in a fault or overload. The maintenance bypass is a manually operated path, usually mechanically interlocked, used to isolate the UPS completely for service. They fail in different ways, and the maintenance bypass being left in the wrong position after earlier work is a common cause of a bypass alarm.

Standards and references

  • ▪IEC 62040-1 — UPS general and safety requirements
  • ▪IEC 62040-3 — UPS performance and test requirements, including transfer and bypass behaviour
  • ▪ISO 8528 — generating sets, including performance classes for frequency behaviour relevant to synchronisation
  • ▪The UPS manufacturer's documentation for the specific unit, which defines the bypass acceptance windows, synchronisation limits and the maintenance bypass operating sequence referred to throughout

This guidance is written from engineering principle and is not a substitute for the manufacturer's model-specific documentation. Where a figure is model-specific, confirm it against the service data for your unit before acting on it.

Need this diagnosed properly?

Send us the make, model and any fault codes shown, and photographs of the controller display if you have them. Our mobile workshop covers all 47 counties.

Call 0768860665WhatsApp the fault detailsRequest a site inspection

Related diagnosis guides

  • ats not changing over
  • safe isolation and proving dead
  • ups inverter fault diagnosis
  • ups not charging batteries
  • ups on battery with mains present